Liquid Heat Exchanger

heat-exhanger-header-wide2250x225

Liquid Heat Exchanger

Heat Exchangers from BV Thermal SystemsThe Liquid Heat Exchanger is designed for highly efficient heat transfer by providing closed loop circulation of temperature controlled coolant.  Controlled temperature coolant is circulated from an enclosed reservoir by a high reliability pump.  The heavy duty design makes it ideal for demanding commercial and industrial  applications where high performance and low maintenance are important.

The Liquid Heat Exchanger from BV Thermal Systems removes heat from the circulating coolant (via a water to water heat exchanger) and transfers the heat to either tap or facilities water.   The actual temperature of the circulating coolant is controlled by a temperature controller and solenoid valve.  Due to varying water supplies, a gate valve is also used to regulate flow/pressure of the facility or house water supply.

Liquid Heat Exhanger Specifications

MODEL HRE200 HRE400
Cooling Capacity 20,000 watts @5°C⌂ 40,000 watts @5°C⌂
Stability ±1.0°C ±1.0°C
Temperature Range 5°c to +50°c 5°c to +50°c
Pump 2.2 GPM to 60 PSI 4.2 GPM to 60 PSI
Reservoir Volume 1.3 gal 1.3 gal
Dimensions (w x d x h) in 14.5 x 22 x 29 14.5 x 22 x 29
Power Requirements 115V, 5A 115V, 7A
Weight (lbs) 50 60


MODEL HRE500 HRE1000
Cooling Capacity 50,000 watts @5°C⌂ w/12 GPM supply 100,000 watts @10°C⌂ w/15 GPM supply
Stability ±1.0°C ±1.0°C
Temperature Range 5°c to +50°c 5°c to +50°c
Pump 7 GPM to 40 PSI 10 GPM to 40 PSI
Reservoir Volume 2 gal 2 gal
Dimensions (w x d x h) in 22 x 30 x 28.5 24 x 29.5 x 37
Power Requirements 200-230V, 10A 200-230V, 10A
Weight (lbs) 100 110

Features of Liquid Heat Exchangers

•Reduces Particulates in Air
•High and Low Alarm with remote signal
•Quiet
•Liquid Filled Pressure Gauge
•Energy Efficient
•± 1°C Accuracy

More Information on the Liquid Heat Exchanger

The Liquid Heat Exchanger features a bypass loop which is an externally adjustable pressure bypass valve located on the front panel.  When actuated, partial or full pump flow will be re-directed through the refrigerated plate heat exchanger back to the reservoir.  This protects the fluid pump and motor from a “dead-head” situation.

Realizing more energy savings than traditional chillers with compressors, the Liquid Heat Exchanger provides continuous cooling capacities to 100,000 watts.  Providing a clean, closed-loop water cooling system  and featuring the highest quality plumbing in the industry, the Liquid Heat Exchangers have a 5°C to 50°C temperature range and provide exceptional temperature control with ±1°C accuracy.

Featuring user adjustable temperature high and low alarm with a remote signal and a reservoir drain with ball valve and liquid filled pressure gauge in PSI and Kpa, the Liquid Heat Exchanger is built to last.  With the largest selection of options in the industry, the Liquid Heat Exchanger may be designed and manufactured to your exact requirements and specifications.